| Documents | |||
| Spec Sheet |
|
||
| Outline Drawing |
|
||
| Operators Manual |
|
||
| Generator Ratings | |||
| Hertz | 60 | ||
| Fuel | Diesel | ||
| kW | 32.0 | ||
| kVA Single Phase | 32.0 | ||
| kVA Three Phase | 40.0 | ||
| RPM | 1800 | ||
| AC Voltage Available |
120/240 120/208 |
||
| AC Amps |
267.0/133.0 111.0 |
||
| Single Phase | |||
| Three Phase | |||
| AC Voltage | 120 | ||
| Voltages-Single Phase Amperes | |||
|
120/240 - 267.0/133.0 |
|||
| Voltages-Three Phase Amperes | |||
|
120/208 - 111.0 |
|||
| Dimensions | |||
|
Weight-Dry (Pounds)
|
1380.0
|
||
|
Length (Inches)
|
53.5
|
||
|
Width (Inches)
|
24.5
|
||
|
Height (Inches)
|
30.0
|
||
| Average Fuel Consumption | |||
|
No Load (Gal/h)
|
0.6
|
||
|
Quarter Load - 25% (Gal/h)
|
1.0
|
||
|
Half Load - 50% (Gal/h)
|
1.5
|
||
|
Three-Quarter Load - 75% (Gal/h)
|
2.0
|
||
|
Full Load (Gal/h)
|
3.0
|
||
| Engine Detail | |||
| Number of Cylinders/Type | 4/4-cycle, IDI | ||
| Cooling System Type | Water | ||
| Maximum Power (hp) | 52.8 | ||
|
Oil Capacity (Quarts)
|
11.0
|
||
| Sound Level 3 Feet in dB(A) Full Load | 68 | ||
| Comments | |||
| Other single phase and three phase voltages are available. Dimensions and sound level are for optional sound shield. Switchable between 50 and 60 Hz. Bulkhead connections. |
|
Marine QD 60 Hz 32 kW MDKBU Spec: A |