GDYJ-502 Hot Sale 100kV Insulating Oil Dielectric Strength Transformer Oil Bdv Tester
Overviews:
-
GDYJ-502 Hot Sale 100kV Insulating Oil Dielectric Strength Tester is used for transformer oil / insulating oil dielectric strength / breakdown voltage testing.
-
The max. output voltage is 100kV.
-
With IEC60156, IS6792, BS5874, ASTM D1816, ASTM D877 test methods.
Introduction:
-
It is developed according to the national standard IEC156 Insulating Oil Dielectric Strength Testing Method;
-
It has large LCD display, micro-printer and can store 100 groups data;
-
It is multi-functional, stable, and easy for operation;
Features:
-
LCD screen can display test procedure and test result;
-
All the human interaction operations complete by the rotating mouse;
-
It is very easy for customers to measure the breakdown voltage of all kinds of oil;
-
You can print the test result by the micro printer internal the tester;
-
Meanwhile, you can upload the test data to PC from RS232 for data analyzing;
-
The special circuit design makes the tester has a good performance at stability and anti-noise;
Specifications:
GDYJ-502 Hot Sale 100kV Insulating Oil Dielectric Strength Transformer Oil Bdv Tester
Output Voltage
|
AC 0V~100KV
|
Rate of Voltage Rise
|
0.5kv/s±5%, 2kv/s±5%, 3kv/s±5%,5kv/s±5%
|
Max Test Times Setting for User-defined Mode
|
9
|
Stir Time Setting for User-defined Mode
|
0~999s
|
Waiting Time Setting for User-defined Mode
|
0~999s
|
Test Error
|
3%RDG+0.3%FS
|
Display
|
256´128 LCD
|
Maximum Storage Capacity
|
100 groups of test data
|
Power Supply
|
AC220V±10%, 50Hz/60Hz
|
Working Environment
|
0-50℃, ≤80%RH
|
Size
|
620 mm*430mm*330mm
|
Weight
|
41kg
|
Functions:
-
Breakdown test of user-defined;
-
Proof test;
-
IEC60156/IS6792/BS5874 test;
-
ASTM D1816 standard test;
-
ASTM D877 standard test;
-
5 minutes standard test;
-
Manual test;
-
Calibration interface for customers;
-
Uploading data to PC and making word report automatically;
-
Result print.