range of product | Modicon Quantum automation platform | |
---|---|---|
product or component type | Safety dc discrete output module |
discrete output number | 16 | |
---|---|---|
group of channels | 1 | |
discrete output logic | Positive logic (source) | |
addressing requirement | 4 output words 7 input words | |
discrete output voltage | 19.2...30 V DC | |
absolute maximum output | 34 V | |
voltage drop | <= 0.3 V 0.5 A | |
sensor power supply | 19.2...30 V | |
maximum load current | <= 0.65 A each point <= 10.04 A each group | |
surge current | 2 A for 10 ms | |
response time | <= 20 ms at state 0 to state 1 <= 20 ms at state 1 to state 0 | |
leakage current | 0.5 mA 30 V | |
protection type | With | |
load inductance | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) 0.5 8 Hz | |
fault indication | Channel fault Overload Power supply fault System fault | |
associated fuse rating | 10 A | |
isolation between channels and bus | 1500 Vrms for 1 minute | |
isolation between group and bus | 1500 Vrms for 1 minute | |
power dissipation | 1.9 W + 0.65 I² | |
marking | CE | |
local signalling | 1 LED green bus communication is present (Active) 1 LED red external fault detected (F) 16 LEDs green output status 16 LEDs red system failure, diagnostic of internal channel fault | |
bus current requirement | 350 mA |
product certifications | CSA CSA HazLoc C-Tick TÜV Rheinland (SIL2) UL |
---|
Sustainable offer status | Green Premium product | |
---|---|---|
RoHS (date code: YYWW) | Compliant - since 0749 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity | |
REACh | Reference not containing SVHC above the threshold | |
Product environmental profile | Available </..LI:characteristics-list__item>#id::#::#p_Doc_Oid\" style=\"outline: 0px; color: rgb(66, 180, 230); cursor: pointer; display: inline-block;\">End of life manual | |
Product end of life instructions | Available |