range of product | Modicon Quantum automation platform | |
---|---|---|
product or component type | Latch/interrupt module |
number of inputs | 16 | |
---|---|---|
discrete input type | Fast isolated | |
absolute maximum input | 30 V DC | |
voltage state 0 guaranteed | -3...5 V | |
voltage state 1 guaranteed | 15...30 V | |
current state 0 guaranteed | 2...8 mA | |
current state 1 guaranteed | <= 0.5 mA | |
response time | 130 µs Off-On 30 µs On-Off | |
reverse polarity protection | Internal in 30 V | |
isolation between channels | 500 V for 60 s AC | |
isolation between channels and bus | 1780 V for 60 s AC | |
bus current requirement | 400 mA | |
power dissipation | 2.0 W + (0.3 x number of points on) | |
mounting support | Backplane for local architecture | |
marking | CE | |
module format | Standard |
resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2 | |
---|---|---|
resistance to electromagnetic fields | 10 V/m 80...2000 MHz conforming to IEC 801-3 | |
ambient air temperature for operation | 0...60 °C | |
ambient air temperature for storage | -40...85 °C | |
relative humidity | 95 % without condensation | |
operating altitude | <= 5000 m | |
standards | UL 508 | |
product certifications | CSA Class 1 Division 2 C-Tick DNV FM Class 1 Division 2 GOST UL |
Sustainable offer status | Green Premium product | |
---|---|---|
RoHS (date code: YYWW) | Compliant - since 0901 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity | |
REACh | Reference not containing SVHC above the threshold | |
Product environmental profile | Available </..LI:characteristics-list__item>#id::#::#p_Doc_Oid\" style=\"outline: 0px; color: rgb(66, 180, 230); cursor: pointer; display: inline-block;\">End of life manual | |
Product end of life instructions | Available |