pH/ ORP, Free Active Chlorine, Temperature Measuring & Control Instruments
chlorine (HOCl, HOBr or ClO2 ) & temperature
KAPTA 2000 Water Quality Controller
The KAPTA 2000 controller has been designed specifically for the industrial and water treatment markets and, coupled with the KAPTA 2000-AC2
The controller is equipped with all the key functions required to provide the user with flexibility for set-up, measurement and control of systems from simple chlorine measurement and recording
right through to industrial process control and chemical dosing.
The KAPTA 2000 controller is capable of measuring chlorine, ORP, pH and temperature and is fitted with 2 current outputs, 4 relays and P.I.D. functionality allowing up to 6 external points to be
measured or controlled. Operation of the controller is simple with a 128x64 pixel resolution graphic display providing continuous readout of chlorine / temperature measurement and status of the
control output devices, selectable in a choice of 5 different languages (English, French, German, Italian and Spanish).
The controller is IP66 rated, wall mounted and equipped for RS485 serial port communication for remote monitoring and data storage. On-board software is designed for 2 point calibrations to ensure
accuracy, reliable performance and sensor diagnostic information.
KAPTA 2000 Water Quality Controller Benefits
• Real-time water network monitoring
• No on-going membrane / electrolyte maintenance
• Chemical free operation
KAPTA 2000 Water Quality Controller Main features
• Amperometric sensor
• Measurement of the main disinfection species: HOCl, HOBr or ClO2
• User replaceable sensing head
• Inline monitoring at up to 10 bar pressure
• Easy conditioning
• 1 year shelf life
KAPTA 2000 Water Quality Controller Typical applications
• Water quality control
• Drinking water security
• Industrial process control
• Chemical dosing measurement and control
• RO membrane security
• Swimming pool water quality
• Cooling towers
• Fish farming
KAPTA 2000 Water Quality Controller Specifications (Controller)
General specifications |
• Measurement of free chlorine or active chlorine (HOCl), temperature (PT 1000) and pH (optional) • Simultaneous display of chlorine and temperature • Wall mounted • Internal flash 4 Mbit memory • PID adjustment and control • Serial output RS485 modbus RTU • 2 Programmable analogue outputs |
||
Display |
Back-lit LCD 128x64 pixel |
Sensor Inputs |
|
Analogue Inputs |
Measurement and Measurement / Control |
Digital Communication |
Serial RS485 Modbus RTU |
4 - 20mA Outputs |
|
Relay Outputs |
|
Measurement accuracy |
±2.5% F.S. (chlorine) ±1.0% F.S. (temperature) |
Dimensions |
144mm x 144mm x 122.5mm |
Operating temperature range |
-10 to +130 degrees C |
Electrical Rating |
IP66 |
Weight |
1 Kg |
Power Consumption |
< 7 W |
Enclosure material |
ABS, Grey RAL 745 (body) Polycarbonate, UV resistant (Frontal) |
Power Rating |
100 to 240 Vac |