ECO-SURE (2E) Carbon Monoxide (CO) Gas Sensor Description
ECO-SURE (2E) Carbon Monoxide Sensor
ECO-SURE (2E) Carbon Monoxide (CO) Gas Sensor Features:
• Long Life
• Stable Performance
• UL Certified - UL2075
ECO-SURE (2E) Carbon Monoxide (CO) Gas Sensor Applications:
• Residential
• Fire Detection
• Ventilation Control
ECO-SURE (2E) Carbon Monoxide (CO) Gas Sensor Technical Specifications
| MEASUREMENT | |
| Operating Principle | 2-electrode electrochemical |
| Measurement Range | 0-500 ppm CO |
| Maximum Overload | 1000 ppm CO |
| Sensitivity | 45 ± 15 nA/ppm |
| Sensitivity Banding | A : 30.0 - 35.9 nA/ppm B : 36.0 - 42.9 nA/ppm C : 43.0 - 50.9 nA/ppm D : 51.0 - 60.0 nA/ppm |
| Response Time (T90) | <30 seconds |
| Baseline Offset (clean air) | -2 to 4 ppm equivalent |
| Zero Shift* (-10°C to +50°C) | < +10 ppm equivalent |
| Repeatability | < ±5% |
| Linearity | Within ±5% |
| | |
| ELECTRICAL | |
| Recommended Load Resistor | 5 Ω |
| Bias Voltage | Not required |
| | |
| MECHANICAL | |
| Housing Material | Noryl N110 |
| Weight | 5 g (nominal) |
| Orientation | Any |
| | |
| ENVIRONMENTAL | |
| Operating Temperature Range*: Continuous Intermittent | -10°C to +50°C -20°C to +50°C |
| Operating Pressure Range | 1 atm ± 10% |
| Operating Humidity Range*: Continuous Intermittent | 15% to 90% RH non-condensing 0% to 99% RH non-condensing |
| | |
| INTRINSIC SAFETY DATA* | |
| Maximum at 1000ppm | 0.1 mA |
| Maximum o/c Voltage | 1.3 V |
| Maximum s/c Current | <1.0 A |
| | |
| LIFETIME | |
| Long Term Output Drift | < 5% per annum |
| Recommended Storage Temp | +10°C to +30°C |
| Expected Operating Life* | > 6 years in normal use from date of manufacture |
| Storage Life | 6 months in original packaging |